Data Center Water Consumption Calculator  

Data Center Water Consumption Calculator
Total Data Center Electricity
Select Unit
Cooling Power
0
Water UseSystem Requirement
0
Water ConsumptionPer Day
0
Water Consumption Per Month
0
Water Consumption Per Year
0

Calculator Assumptions

  • 40% of data center energy is used for cooling

  • Each 1,000 kilowatts of cooling load requires 1,027 US gallons per minute of condenser water flow through the evaporative cooling towers

    • Cooling system utilizes 3 imperial gallons per minute of condenser water per ton of cooling

  • Evaporation consumes about 1% of condenser water flow

  • Drift and blowdown consume about .5% of condenser water flow

  • 1 Acre-foot = 325,851 US gallons

  • System is running at peak capacity at all times